NEC Voltage Drop Calculator
Calculate single-phase and three-phase voltage drop in volts and percent using NEC Chapter 9 Table 8 resistance, verify 3% branch / 5% total limits, and find the minimum AWG.
NEC Chapter 9 Table 8 Conductor Resistance & Voltage Drop Formulas
DC resistance at 75°C (Ω per 1,000 ft) used to verify NEC 210.19(A) 3% branch / 5% total voltage drop limits:
| Wire Size | Copper R (Ω / 1,000 ft) | Aluminum R (Ω / 1,000 ft) | Max 1φ 120V Run @ 15A (≤3%) |
|---|---|---|---|
| 14 AWG | 3.140 | — | 38 ft (Cu) |
| 12 AWG | 1.980 | 3.250 | 60 ft (Cu) |
| 10 AWG | 1.240 | 2.040 | 96 ft (Cu) |
| 8 AWG | 0.778 | 1.280 | 154 ft (Cu) |
| 6 AWG | 0.491 | 0.808 | 244 ft (Cu) |
| 4 AWG | 0.308 | 0.508 | 389 ft (Cu) |
| 2 AWG | 0.194 | 0.319 | 618 ft (Cu) |
| 1/0 AWG | 0.122 | 0.201 | 983 ft (Cu) |
Formulas: Single-phase VD = (2 × L × I × R) ÷ 1,000 · Three-phase VD = (1.732 × L × I × R) ÷ 1,000, where L is one-way feet and I is load amps.
Use Conduit Bend Calc 100% offline on the jobsite
Frequently Asked Questions
What is the NEC 3% and 5% voltage drop recommendation?
NEC 210.19(A) Informational Note recommends keeping voltage drop to 3% or less on branch circuits and 5% or less combined across the feeder and branch circuit. Staying within 3% prevents motor overheating, dimmed lights, and nuisance equipment trips.
What is the formula for single-phase vs three-phase voltage drop?
Using NEC Chapter 9 Table 8 DC resistance R (ohms per 1,000 ft): single-phase VD = (2 × L × I × R) ÷ 1,000, and three-phase VD = (1.732 × L × I × R) ÷ 1,000, where L is one-way run length in feet and I is load current in amps.
How do copper and aluminum affect voltage drop?
Copper has lower resistance (approximately K ≈ 12.9 Ω·cmil/ft) than aluminum (K ≈ 21.2 Ω·cmil/ft). For the same wire size, current, and run length, aluminum drops about 64% more voltage than copper, so long aluminum runs usually step up one or two wire sizes.
How do I upsize AWG to stay under 3% voltage drop?
If calculated voltage drop exceeds 3%, step up to the next larger wire gauge (lower AWG number or larger kcmil) until drop falls at or below 3%. This calculator automatically shows the smallest compliant copper or aluminum wire size when your run is over limit.
Do I enter one-way distance or total round-trip wire length?
Always enter the one-way distance from the panel or source to the load (in feet or meters). The single-phase factor (2) and three-phase factor (√3 ≈ 1.732) already account for the return path.